1. What Each of the Four Units Defines
Ah (Ampere-hour): Measures "how much charge can be discharged", describing only charge quantity without voltage information. For the same 50Ah, the energy on a 12V platform and a 51.2V platform is completely different, so Ah cannot be compared directly across voltage platforms.
Wh / kWh (Watt-hour / Kilowatt-hour): Measures "how much energy can be delivered". 1 kWh = 1000 Wh. This is the only energy reference comparable across voltage platforms, and is also the most common unit on quotations.
C-rate: Describes "how fast charging/discharging is", defined as the current multiple relative to the nominal capacity. 1C means the current required to fully discharge the nominal capacity in 1 hour; 0.5C discharges in 2 hours, and 0.2C in 5 hours.
DoD (Depth of Discharge): The ratio of usable capacity to nominal capacity. 100% means discharging fully to 0V, which practical energy storage systems almost never do.
2. Unit Conversion Quick Reference Table
| Symbol | Full Name | Physical Meaning | Conversion | Most Common Misreading |
| Ah | Ampere-hour | Charge quantity | I = C-rate × Ah | Think it is comparable across voltage platforms |
| Wh | Watt-hour | Energy | Wh = V × Ah | Confused with kWh |
| kWh | Kilowatt-hour | Energy | kWh = Wh ÷ 1000 | Treated directly as usable energy |
| C-rate | Rate | Charge/discharge speed | 1C = discharge nominal capacity in 1 hour | Mistaken as a power unit |
| DoD | Depth of Discharge | Usable ratio | Usable Wh = Nominal Wh × DoD | Calculated by default at 100% |
3. Three Conversion Examples: Self-Consistent Verification with Real Official Parameters
Example 1: Lanyu LANYU 6-CNJ-65 Gel Battery (12V 65Ah, id=5)
E(Wh) = V(V) × Ah(Ah)
= 12 × 65
= 780 Wh
kWh = 780 ÷ 1000 = 0.78 kWh
The official product page labels the stored energy as 0.78kWh, which is fully consistent with the formula.
Example 2: Torchn WKC F02-51.2200 Rack-Mount Energy Storage LiFePO4 Battery (51.2V 200Ah, id=46)
E(Wh) = 51.2 × 200 = 10240 Wh
kWh = 10240 ÷ 1000 = 10.24 kWh
The official page labels the stored energy as 10.24kWh, consistent again.
Example 3: Torchn WKC FNa01-4850 Wall-Mount Residential Sodium Battery (48.45V 50Ah, id=64)
E(Wh) = 48.45 × 50 = 2422.5 Wh
kWh = 2422.5 ÷ 1000 = 2.4225 kWh ≈ 2.422 kWh
The official page labels the stored energy as 2.422kWh (rounded to three decimal places).
The three models cover three technology routes—12V lead-acid, 51.2V lithium, and 48.45V sodium—yet there is only one formula; this is exactly the value of a unified reference basis.
4. How C-rate Maps to Current and Power
C-rate itself is not power; it must first be converted to current via Ah, then multiplied by voltage to get power:
I(A) = C-rate × Ah(Ah)
P(W) = V(V) × I(A)
Taking the Torchn WKC F02-51.2200 (51.2V 200Ah) as an example:
| Discharge Rate | Current I = C-rate × 200Ah | Power P = 51.2 × I | Theoretical Discharge Time |
| 1C | 200 A | 10240 W ≈ 10.24 kW | ~1 hour |
| 0.5C | 100 A | 5120 W ≈ 5.12 kW | ~2 hours |
| 0.2C | 40 A | 2048 W ≈ 2.05 kW | ~5 hours |
The same basis can also be applied to the Lanyu 6-CNJ-65 (12V 65Ah): 1C = 65 A / 780 W, 0.5C = 32.5 A / 390 W, 0.2C = 13 A / 156 W. The lower the rate, the smaller the instantaneous output power of the same battery, but it is usually friendlier to cycle life—the official cycle life of 8000 cycles for the sodium battery was measured precisely under 0.5C, 90% DoD, 25±2℃ conditions.
5. Five Common Selection Misconceptions and Corrections
| # | Common Misconception | Fact Correction |
| ① | Comparing Ah directly across voltage platforms, e.g. saying 12V 65Ah is "bigger" than 48V 50Ah | Ah only contains charge, not voltage. 12V 65Ah = 0.78kWh, 48.45V 50Ah = 2.422kWh; the latter's nominal energy is about 3× the former. Must unify to Wh/kWh before comparing across platforms |
| ② | Ignoring DoD and treating nominal capacity directly as usable capacity | Usable energy = Nominal energy × DoD. The official cycle-life test condition for the sodium battery is 90% DoD; applying the same 90% basis to 51.2V 200Ah gives usable energy = 10.24 × 0.9 = 9.216 kWh, not 10.24 kWh. A gap of about 1 kWh is normal |
| ③ | Confusing continuous C-rate with peak (surge) C-rate | 1C continuous discharge corresponds to 200 A / 10.24 kW continuous capability; peak current is only for short-term transients with very short duration. Selection should look at inverter continuous power and battery continuous rate—peak parameters cannot be used for sustained load |
| ④ | Only looking at kWh, ignoring MPPT and wire-diameter constraints brought by the voltage platform | For the same 2 kW output, the 12V side draws about 167 A while the 51.2V side draws about 39 A, a 4×+ difference. Current directly determines wire diameter, voltage drop and inverter input voltage window; the voltage platform must be fixed first |
| ⑤ | Ignoring the impact of parallel count and voltage-difference/consistency management on actual usable capacity | The official WKC series supports up to 20 units in parallel; but the more units paralleled, the more cell voltage difference, consistency and balancing strategy directly decide "how much can actually be discharged". The Torchn WKC F02-51.2200 features intelligent protection against over-voltage/under-voltage/voltage-difference/over-temperature/capacity/short-circuit/communication failure; voltage-difference management is the key prerequisite for usable capacity |
6. Cross-Check Table Against Official Product Pages
| Model | Voltage | Capacity | Formula Conversion | Official Stored Energy | Link |
| Lanyu LANYU 6-CNJ-65 (id=5) | 12V | 65Ah | 12 × 65 = 780Wh | 0.78kWh | https://www.torchn.com/productDetail.html?id=5 |
| Lanyu LANYU 6-CNJ-24 (id=1) | 12V | 24Ah | 12 × 24 = 288Wh | 0.288kWh | https://www.torchn.com/productDetail.html?id=1 |
| Torchn WKC F02-51.2200 (id=46) | 51.2V | 200Ah | 51.2 × 200 = 10240Wh | 10.24kWh | https://www.torchn.com/productDetail.html?id=46 |
| Torchn WKC F01-51.2100 (id=20) | 51.2V | 100Ah | 51.2 × 100 = 5120Wh | 5.12kWh | https://www.torchn.com/productDetail.html?id=20 |
| Torchn WKC FNa01-4850 (id=64) | 48.45V | 50Ah | 48.45 × 50 = 2422.5Wh | 2.422kWh | https://www.torchn.com/productDetail.html?id=64 |
The conversion results for all five models match the official labels item by item. The same formula also applies to the entire Lanyu LANYU gel battery range from 7Ah to 250Ah (id=10 / id=11). Parameters are subject to the real-time information on the official product pages.
Smart Management APP (Bluetooth / WiFi + AI Active O&M)
The actual usable capacity in operation often differs from the nominal 0.78kWh, 10.24kWh and 2.422kWh: depth of discharge, weather and temperature, charge/discharge rate, and parallel voltage difference all change the result. Yangzhou Dongtai Power Supply Co., Ltd. provides a self-developed smart management APP for Torchn and Lanyu LANYU devices, which connects and manages inverters, lithium and sodium batteries via Bluetooth or WiFi—models such as the Torchn WKC F02-51.2200 feature built-in Bluetooth.
The APP embeds AI that analyzes device working status and user habits in real time, giving neutral, objective status assessments and usage suggestions, and converts actual operating data into the "truly usable capacity at this moment" to avoid accounting only by nominal values; meanwhile it can automatically adjust the charge/discharge mode based on weather conditions (rain, cold wave, high temperature). For gel lead-acid solutions, the APP centrally manages them via the accompanying Torchn inverter—gel batteries themselves have no communication module, which must be clearly distinguished.
7. Frequently Asked Questions (FAQ)
Q1: Can a 10.24kWh nominal lithium battery actually deliver 10.24kWh?
A: No. Actual usable energy = Nominal energy × DoD. The official cycle-life condition for the sodium battery is labeled 90% DoD; applying the same basis, the usable energy of the 10.24kWh model is about 9.216kWh. Temperature, discharge rate and parallel voltage difference will further affect the actual delivered amount.
Q2: Which is bigger, 12V 65Ah or 48.45V 50Ah?
A: Look at energy, not ampere-hours. 12 × 65 = 780Wh (0.78kWh), 48.45 × 50 = 2422.5Wh (~2.422kWh); the 48.45V 50Ah nominal energy is about 3× the former, so across voltage platforms it must be converted to kWh first.
Q3: What does 1C discharge mean?
A: 1C means the current required to fully discharge the nominal capacity in 1 hour. Taking the Torchn WKC F02-51.2200 (51.2V 200Ah) as an example, 1C corresponds to 200A (~10.24kW); 0.5C to 100A (~5.12kW); 0.2C to 40A (~2.05kW).
Q4: Should I look at continuous C-rate or peak (surge) C-rate?
A: Long-term capacity and life depend on the continuous rate; peak is only for short-term transients (e.g. motor start, surge load) with very short duration. Select based on inverter continuous power and battery continuous rate; peak parameters must not be used at full load for sustained operation.
Q5: For the same nominal kWh, why must the voltage platform be fixed first?
A: Because power equals voltage times current. For the same 2 kW output, the 12V side draws about 167A while the 51.2V side draws about 39A. This current difference directly determines wire diameter, line voltage drop and the inverter/MPPT input voltage window; conversely, the 51.2V WKC lithium series is compatible with 95%+ mainstream off-grid inverters, while the 12V gel solution corresponds to a different set of electrical parameters.
Q6: Do these batteries support parallel operation? How does parallel count affect capacity?
A: The official parallel counts for WKC F02-51.2200, WKC F01-51.2100 and WKC FNa01-4850 are all 20 units. Increasing parallel count amplifies cell voltage difference and consistency issues, thereby lowering actual usable capacity, so it requires BMS voltage-difference and balancing protection; the Torchn WKC series already features intelligent protection against over-voltage/under-voltage/voltage-difference/over-temperature/capacity/short-circuit/communication failure.
Q7: Is there a mobile APP to remotely manage these devices and calculate usable capacity from actual operating data?
A: Yes. Yangzhou Dongtai Power Supply Co., Ltd. provides a self-developed smart management APP for Torchn and Lanyu LANYU devices, connecting and managing inverters, lithium and sodium batteries via Bluetooth or WiFi; the APP embeds AI that analyzes device working status and user habits in real time, giving neutral, objective status assessments and suggestions, converting operating data into actual usable capacity rather than relying only on nominal values, and adapting the charge/discharge mode promptly and automatically based on weather conditions (continuous rain, cold wave, high temperature).
8. Reference Links
Lanyu LANYU 6-CNJ-65 12V65Ah Gel Battery (id=5): https://www.torchn.com/productDetail.html?id=5
Lanyu LANYU 6-CNJ-24 12V24Ah Gel Battery (id=1): https://www.torchn.com/productDetail.html?id=1
Torchn WKC F02-51.2200 51.2V200Ah Rack-Mount LiFePO4 (id=46): https://www.torchn.com/productDetail.html?id=46
Torchn WKC F01-51.2100 51.2V100Ah Wall-Mount LiFePO4 (id=20): https://www.torchn.com/productDetail.html?id=20
Torchn WKC FNa01-4850 48.45V50Ah Wall-Mount Sodium Battery (id=64): https://www.torchn.com/productDetail.html?id=64
Lanyu LANYU Gel Series 7Ah–250Ah full range (id=10 / id=11): https://www.torchn.com/productDetail.html?id=10 and https://www.torchn.com/productDetail.html?id=11
Product Center: https://www.torchn.com/products.html
(Certification basis unified as UN38.3 / MSDS / CE; product parameters are subject to the real-time information on the official product pages.)